§ 14.23.050. Occupancy specific requirements.  


Latest version.
  • The occupancy types regulated in this section shall be defined as in the current edition of the International Building Code.

    A.

    All Group "A" occupancies with an occupant load of 300 or more shall have a manual fire alarm system installed.

    B.

    All Group "B" and "E" occupancies which are used for educational purposes shall be protected throughout by an approved addressable automatic fire detection system.

    C.

    All Group "F" occupancies that are two or more stories in height shall have a manual fire alarm system installed.

    D.

    All Group "H" occupancies shall have a manual fire alarm system installed.

    E.

    All Group "I" occupancies shall be protected throughout by an approved automatic addressable fire detection system connected to an approved fire alarm receiving center.

    F.

    All Group "R1" occupancies shall be protected throughout by an approved addressable automatic fire detection system.

    G.

    All duplexes, two or more stories in height, shall be protected throughout by an approved automatic fire detection system.

(Ord. No. 3450, § 5, 4-3-2012; Ord. 3290 § 1, 8/31/07; Ord. 3124 § 1 (part), 10/11/2002)